One set, 1,000 kW and up
1 megawatt generator rental.
The rental list has single sets from 1,250 kW to 1,900 kW. This page covers what a megawatt means at the breaker, which of those sets fits, and when three smaller units beat one large one.
For multi-megawatt sites and load that arrives in phases, see megawatt generator rentals.

At the breaker
What 1,000 kW is in current.
A megawatt sounds like one number, but the cable, breaker and switching are all sized from the current, and the current depends on the voltage. At a 0.8 power factor, 1,000 kW is 1,250 kVA.
The kW printed on a listing may be a standby, prime or continuous figure, and a set's model name can be its kVA, its kW or neither. Read the data plate before putting two sets side by side. Heat and altitude take something off the top as well, and the derate for your site is stated in the quote.
| Voltage | Amps at 1,000 kW | In practice |
|---|---|---|
| 208 V | 3,470 A | Too much current to be practical. Sets this size are not built for it. |
| 480 V | 1,504 A | The voltage most large rental sets are built for. |
| 600 V | 1,203 A | Most Canadian industrial plants, at 347/600 V. |
Three-phase, full load, 0.8 power factor. A 480 V set feeding a 600 V plant goes through a step-up transformer; see transformer rentals. For other loads, use the amperage calculator.
One set or three
A single megawatt set against three NPI350s.
Three 350 kW units in parallel carry 1,050 kW, so a megawatt load can go either way. These are the differences that usually settle it.
| Question | One 1 MW+ set | Three NPI350s in parallel |
|---|---|---|
| How it arrives | One container on a semi-trailer, one pad, one set of connections. | Three packages, each moved and placed separately. |
| The load it suits | Load that is all there from the first day. | Load that grows, or a site that must keep running when one engine stops. |
| Oil changes and repairs | The site goes down for them, or a second set stands by. | One unit comes off and the other two carry on, if the load allows. |
| Light early load | One large engine runs well below its rating until the load arrives. | Units are switched off to match the load, so each runs nearer its rating. |
| Connection | One large breaker and a heavy cable run. | A paralleling bus, with the controllers sharing load between the sets. |
Paralleling is built into the controllers of the NPI Series. Pairing two of the large sets is confirmed for the exact units first. How blocks are phased in as a site grows is on megawatt generator rentals.
On the rental list
Sets of 1 MW and up, with their full-load current.
Read from the inventory every hour. Current is worked out from each listing's kW at a 0.8 power factor, and shown where the listing gives a single voltage.
| Unit | Output | Fuel | Voltage | Full-load amps |
|---|---|---|---|---|
| Caterpillar XQ1250G Natural Gas Generator Set | 1,250 kW | Natural gas | 480 V | 1,879 A |
| Used XQ1475 kW Natural Gas Generator | 1,475 kW | Natural gas | 480 V | 2,218 A |
| 1900 kW Natural Gas / Propane Generator | 1,900 kW | Gas or propane | On request | On the quote |
Before it carries the site
Each set is run against a resistive load bank first. The 1,000 kW bank is the largest on the rental list.
Below a megawatt
Smaller sets, each with its fuel and voltage, are on generators by size. The 350 kW class is on 350 kW generator rental.
Rent or buy
Renting or buying at a megawatt.
At this size the purchase price and the monthly rent are both large, so the term decides it. A load with a known end date rents. A plant that will run on its own generation for years usually comes out ahead owning the set, provided someone is lined up to service it.
Used sets are sold with their history. Where it is known, the listing shows hours since new and when the last major overhaul was done. Those two numbers say more about what is left in the engine than its age does.
The Used XQ1475 kW Natural Gas Generator is offered rent-to-own, so rent paid goes toward buying it.
The full comparison is in renting vs. buying an industrial generator. Servicing an owned set is covered on generator service.
1 MW and up, for sale
- Caterpillar XQ1250G Natural Gas Generator Set1,250 kW · Natural gas
- Used XQ1475 kW Natural Gas Generator1,475 kW · Natural gas
- 1900 kW Natural Gas / Propane Generator1,900 kW · Gas or propane
More gas sets are on used natural gas generators for sale and natural gas generators for sale.
1 MW questions
Asked about a megawatt set.
How many amps does a 1 MW generator put out?
At full load and a 0.8 power factor, about 1,504 A at 480 V and 1,203 A at 600 V. At 208 V the figure would be near 3,470 A, which is why nothing this size is built for it. The breaker, cable and any transformer between the set and the site are sized from the current, so the voltage is settled first.
Is a 1 MW generator the same as 1,250 kVA?
At a 0.8 power factor, yes. kVA is the kW divided by the power factor, so a set that delivers 1,000 kW at 0.8 PF is a 1,250 kVA set. Model names mix the two, so check which one a listing quotes, and whether it is a standby, prime or continuous figure, before comparing sets.
Can one 1 MW set start our largest motors?
That is decided by the engine's load acceptance as much as by its kW. A gas engine takes a sudden block of load in smaller steps than a diesel, so a big motor started across the line pulls voltage and frequency down further. Soft starters and drives shrink the step, and so does starting the biggest motor before the rest of the plant is running. The motor list is checked against the manufacturer's data for the specific set.
Is there a 1 MW diesel generator for rent?
Not at the moment. Every rental set of 1,000 kW or more runs on gas. A diesel load this size is quoted on smaller diesel sets, and whether those can share a bus is checked unit by unit before the quote goes out.
Can a 1 MW generator run on propane?
The 1900 kW Natural Gas / Propane Generator is listed for natural gas or propane. At a megawatt the draw is heavy enough that the tank and vaporisers are planned with the propane supplier before the job is booked, and winter temperatures are part of that plan.
Should we rent or buy a 1 MW generator?
Rent when the load has an end date: a construction phase, a gap until the utility connects, a turnaround. Buy when the set will run for years and someone is in place to service it. Between the two, ask for a rental quote and a purchase quote together and count the months of rent that equal the price.
What does a 1 MW generator rental cost?
No rates are published. The total depends on the set and the rating it runs at, the term, the fuel equipment, distribution rated for 1,500 A or more, load testing and the haul from Red Deer, and each line is itemised in the written quote.
Send the voltage and the biggest motor.
Add the total load, the fuel on site, the dates and whether you might keep the set. The quote comes back naming one set or a block of three, and everything between it and your switchgear.