If the visit finds a fault
The visit report names it, and the repair is quoted on its own so it can be approved separately. Diagnosis on building sets is covered on commercial generator repair.
Commercial generator repairPlanned service for building standby sets
For the generator behind an office, care home, condo, school or store: a set that sits for months and then has to work the first time.
A visit covers the whole standby system, from the transfer switch and batteries to the fuel and the engine, and ends with the set carrying load. Technicians come from Red Deer and work on other makes as well as our own.

What has to work in an outage
A building's generator is one part of a chain. When the power goes out, every link has to hold, and a generator that runs fine on its own can still leave the building dark.
The transfer switch has to notice. A sensing fault or a wrong setting means the generator is never asked to start.
Checked: Voltage sensing and the time delays set on the switch controller.
Most failed starts come down to a tired battery, a charger that stopped charging, or a block heater that let the engine go cold overnight.
Checked: Battery condition under load, charger output, block heater operation.
Old diesel, a clogged filter, or gas pressure that sags once the engine draws hard will stall a set that seemed fine at idle.
Checked: Fuel condition and filters, or the gas supply pressure while the set is loaded.
A set can run perfectly while the switch never moves, or moves and drops the elevator or fire pump because loads come on all at once.
Checked: A real transfer, watched end to end, with load step timing on the controller.
A building that has added rooftop units or a server room since the set was sized can overload it in the first hour.
Checked: Voltage, frequency and temperatures read off while the set carries load.
The switch has to retransfer and the engine has to cool down and shut off. A set that keeps running, or one that dies on retransfer, both mean another call.
Checked: Retransfer, cool-down timer and the return to automatic.
The engine-side checklist, from oil sampling to the protective shutdowns, is on generator service and maintenance. Switch equipment for a temporary changeover is on transfer switch rentals.
Why idle sets wear out
Commercial standby sets can go years with hardly any hours on the meter. Low hours are not the same as low wear, and the schedule has to reflect that.
Batteries, coolant, hoses and belts, and stored diesel all deteriorate whether the engine runs or not. On a standby set that logs a few hours a year, these decide the visit, not the hour meter.
Oil and filters. A standby set rarely reaches an hours-based change, so it is changed on time instead, and the sample drawn at each change starts a record of what the engine is doing inside.
A renovation, a new tenant fit-out or a larger chiller changes what the generator has to carry. After any of those, the next visit should include a test at the new load, not just a start.
Testing in an occupied building
The only way to know a standby set will carry the building is to make it carry something. That can be the building itself, through a planned transfer, or a load bank wired to the generator while the building stays on the utility.
A planned transfer is the more complete test because the switch, the load steps and the building's own equipment are all part of it. It also means a brief interruption, so it is booked with the property manager, and with whoever monitors the fire alarm.
Care homes during the night, a server room mid-quarter, a store at the till: a load bank lets the engine and alternator work hard without the building noticing. The load banks come from the NexSource fleet and are resistive. If your specification asks for reactive load, mention it when booking. See load bank rentals.
Voltage, frequency, temperatures and pressures are written down as the set carries load, so the next visit has something to compare against. The record is yours to hand to an inspector or insurer.
The visit report names it, and the repair is quoted on its own so it can be approved separately. Diagnosis on building sets is covered on commercial generator repair.
Commercial generator repairAn overhaul or a rebuild in the shop leaves the building without backup. A rental set can stand in, connected through a temporary transfer arrangement.
Commercial generator rentalsWhen the repair list keeps growing or the building has outgrown the set, compare the cost of keeping it going with what is in stock to replace it.
Standby generators for saleBooking a visit
NexSource works out of one shop, on Queensgate Crescent in Red Deer. Buildings across Alberta are serviced from there, and travel is shown in the quote. For an industrial site, a lease or a prime-power set, see generator service.
Commercial maintenance questions
Work from the manufacturer's schedule and whatever standard your inspector or insurer holds the building to, then adjust for the unit. Because a standby set runs so little, most of its schedule is set on the calendar. Send the details and the visit plan comes back in writing, showing what is checked on each visit.
Exercising it proves it starts. It does not change the oil, test the batteries under load or check the transfer switch. A diesel set exercised week after week with nothing connected can also start to wet stack, leaving unburned fuel in the exhaust, which a run under real load or a load bank burns off.
Most of a visit is done with the utility carrying the building. A test transfer involves a brief interruption, so it is booked with the property manager in advance, along with whoever monitors the fire alarm. Where a transfer cannot be scheduled, the engine can be tested on a load bank instead.
Yes. Technicians work on other makes as well as the sets NexSource sells and rents. Send the make, model and serial with the booking so the right parts and manual come on the visit.
Yes. Property managers and owners with several sites can have the visits planned together so each unit is seen on schedule and the records sit in one place. What it involves depends on the number of units, where they are and how each runs.
A written record of what was checked, what was replaced, the load test readings and anything that needs attention before the next visit. Oil results are added as they come back from the lab. Keep it for your inspector or insurer; they decide what satisfies their requirements.
It is quoted per job, with no rate card. The number of units, their size and fuel, how far they are from Red Deer, whether a load bank goes along and what each visit covers all affect the price.
Send the nameplate, the hours and what the generator backs up. The quote lists what each visit covers, how often, and whether a load bank comes along.