Skip to content
NPI — NexSource Power Inc.
NexSource Power

Fuel Consumption Chart

Fuel Consumption

This chart approximates the fuel consumption of a diesel generator based on the size of the generator and the load at which the generator is operating. Please note that this table is intended to be used as an estimate of how much fuel is burned during operation and is not an exact representation due to various factors including generator/engine manufacturer, model, age and load.

Diesel (Gal/hr)

Generator Size (kW)25% Load50% Load75% Load100% Load
200.60.91.31.6
301.31.82.42.9
401.62.33.24
601.82.93.84.8
752.43.44.66.1
1002.64.15.87.4
1253.157.19.1
1353.35.47.69.8
1503.65.98.410.9
1754.16.89.712.7
2004.77.71114.4
2305.38.812.516.6
2505.79.513.618
3006.811.316.121.5
3507.913.118.725.1
4008.914.921.328.6
5001118.526.435.7
60013.22231.542.8
75016.327.439.353.4
100021.636.452.171.1

Natural Gas (ft³/hr)

Natural gas burn varies with the engine and the gas, so these figures come from the NPI Series spec sheets, at full load, rather than from a generic curve. Ask for the sheet for any other unit.

UnitOutput (kW)Natural gas at 100% load (ft³/hr)
NPI2502503,086
NPI3503505,346

Propane (Gal/hr)

Generator Size (kW)25% Load50% Load75% Load100% Load
200.871.311.892.32
301.892.623.494.22
402.323.344.655.82
602.614.225.526.98
752.764.946.698.87
1003.785.968.4310.76
1254.57.2710.3213.23
1354.87.8511.0514.25
1505.238.5812.2215.85
1755.969.8914.1118.47
2006.8311.21620.94
2307.712.818.1824.14
2508.2913.8119.7826.18
3009.8916.5323.4131.26
35011.4919.0427.1936.50
40012.9421.6230.9941.59
5001626.938.3951.91
60019.231.9945.8162.24
75023.739.8457.1577.65
100031.4152.9375.76103.39

From burn to storage

Multiply the hourly figure by the hours a day the set runs and the days between fuel deliveries. That is the diesel the site needs on hand, and the size of tank to put beside the generator.

Fuel tank rentals →

Let's power your project.

Built in Red Deer, Alberta · Proudly Canadian

CALL 403-887-4567